Occupant Load Calculator

Enter floor area (sq ft or m²) and a space function to get the occupant load, then add rooms and fixed seating into a mixed-use total with exit-count and egress-width planning checks.

Occupant load = floor area ÷ occupant load factor, the square feet per person that IBC Table 1004.5 assigns to the space function, with any fraction rounded up to a whole person.

Use the Occupant Load Calculator

Space Parameters

Fixed seating (Section 1004.6)

One occupant per seat, per 18 in of bench, per 24 in of booth.

Fixed-seat load: 0

Results

Enter space parameters and click Calculate.

Building / floor total (mixed use)

The occupant load of a floor is the sum of its spaces. Add each room or seating area.

No spaces added yet.

    IBC Table 1004.5 — Occupant Load Factors (2024)

    Same values in the 2018 and 2021 editions except the information technology equipment row. 1 m² = 10.764 sq ft. Fixed seating, malls (Section 402.8.2) and bowling lanes follow their own rules.

    Function of Space sf/occ m²/occ Area Basis
    Assembly without fixed seats — concentrated (chairs only) 7 0.65 net
    Assembly without fixed seats — unconcentrated (tables and chairs) 15 1.39 net
    Assembly without fixed seats — standing space 5 0.46 net
    Stages and platforms 15 1.39 net
    Assembly — gaming floors (keno, slots, etc.) 11 1.02 gross
    Assembly — exhibit gallery and museum 30 2.79 net
    Skating rinks, swimming pools — rink and pool 50 4.65 gross
    Skating rinks, swimming pools — decks 15 1.39 gross
    Library — reading rooms 50 4.65 net
    Library — stack area 100 9.29 gross
    Airport terminal — waiting areas 15 1.39 gross
    Airport terminal — baggage claim 20 1.86 gross
    Airport terminal — baggage handling 300 27.87 gross
    Airport terminal — concourse 100 9.29 gross
    Business areas (offices) 150 13.94 gross
    Concentrated business use (call centers, trading floors; Section 1004.8) 50 4.65 gross
    Courtrooms — other than fixed seating areas 40 3.72 net
    Information technology equipment facilities (new in 2024) 300 27.87 gross
    Educational — classroom area 20 1.86 net
    Educational — shops and other vocational rooms 50 4.65 net
    Day care 35 3.25 net
    Exercise rooms 50 4.65 gross
    Locker rooms 50 4.65 gross
    Industrial areas 100 9.29 gross
    Group H-5 fabrication and manufacturing areas 200 18.58 gross
    Institutional — inpatient treatment areas 240 22.30 gross
    Institutional — outpatient areas 100 9.29 gross
    Institutional — sleeping areas 120 11.15 gross
    Mercantile (sales floor, any story) 60 5.57 gross
    Mercantile — storage, stock, shipping areas 300 27.87 gross
    Residential (dwellings, apartments, hotels) 200 18.58 gross
    Dormitories 50 4.65 gross
    Accessory storage areas, mechanical equipment rooms 300 27.87 gross
    Parking garages 200 18.58 gross
    Warehouses 500 46.45 gross
    Kitchens, commercial 200 18.58 gross
    Agricultural buildings 300 27.87 gross
    Aircraft hangars 500 46.45 gross

    Spaces with one exit (Table 1006.2.1)

    OccupancyMax occupant load
    A, B, E, F, M, U49
    S29
    R-2, R-3, R-420
    R-110
    I-1, I-2, I-3, I-410
    H-4, H-510
    H-1, H-2, H-33

    Common path of egress travel limits in the same table also apply.

    Exits per story and egress width

    Occupant load per storyMinimum exits
    1–5002
    501–1,0003
    More than 1,0004

    Table 1006.3.3; single-exit stories follow Table 1006.3.4. Width: 0.3 in per occupant for stairways and 0.2 in for other components, or 0.2 in and 0.15 in in buildings sprinklered throughout with an emergency voice/alarm communication system (not Group H or I-2).

    Quick answer

    Occupant load = floor area ÷ occupant load factor, the square feet per person that IBC Table 1004.5 assigns to the space function, with any fraction rounded up to a whole person. Use gross or net area as the table specifies, and for a building with several uses add the load of each space.

    Examples

    Use (IBC factor, sf)AreaOccupant load
    Assembly, chairs (7 net)1,400 sf200
    Assembly, tables (15 net)1,500 sf100
    Business/office (150 gross)6,000 sf40
    Mercantile sales floor (60 gross)6,000 sf100
    Classroom (20 net)900 sf45
    Residential (200 gross)2,700 sf14
    Accessory storage (300 gross)3,000 sf10

    Pick a space function, enter the area, and add rooms or fixed seats to build a whole-floor total with exit and egress-width checks.

    Summary

    This planning tool calculates design occupant load using the factors in 2024 IBC Table 1004.5, which match the 2018 and 2021 editions except for the information technology equipment facilities row added in 2024. Areas can be entered in square feet or square meters. Rooms and fixed seating (Section 1004.6: one occupant per seat, 18 inches of bench or 24 inches of booth) can be added into a mixed-use total. The tool shows egress-capacity width components (with the sprinkler and voice/alarm reduction where it applies), an exit-count checkpoint per Table 1006.3.3, and the single-exit space limit per occupancy group from Table 1006.2.1, without claiming code compliance.

    How it works

    1. Select the space function (e.g. assembly, business, mercantile); the occupancy group for the single-exit check is filled in automatically and can be changed.
    2. Enter the floor area in square feet or square meters, using gross or net area as the function requires.
    3. The calculator divides area by the Table 1004.5 factor and rounds any fraction up to a whole occupant.
    4. Click "Add to building total" for each room, and use the fixed-seating box for seats, benches (18 in per person) and booths (24 in per person).
    5. Review the egress capacity widths (0.3 in stairs / 0.2 in other, or 0.2 / 0.15 when sprinklered with an emergency voice/alarm system) and the exit-count checkpoints.

    Use cases

    • Determine occupant load during building permit applications.
    • Total a mixed-use floor, such as a restaurant dining room, kitchen and storage, before sizing exits.
    • Count fixed seats, pews and booths in an assembly space.
    • Check whether a room can have a single exit door for its occupancy group.
    • Estimate egress-capacity width components for early design, sprinklered or not.
    • Convert a metric floor plan (m²) into an IBC occupant load.