Egress Width Calculator
Get the required egress width from the occupant load (the larger of capacity width and the code minimum), split it across exits, or check how many people existing doors and stairs can serve.
Required egress width is the larger of two checks: capacity width (occupant load × 0.3 in per person for stairways, 0.2 in for doors, corridors and ramps, IBC 1005.3) and the dimensional minimum for the component (44 in stair, 32 in clear door, 44 in corridor in most occupancies).
Use the Egress Width Calculator
Egress Inputs
Stairways: the largest single story served, not the sum of all floors.
Enter the occupant load to calculate the required width.
Required egress width
Screening only
Exit count, remoteness, travel distance, accessibility, hardware, door-swing encroachment and local amendments are not checked. Verify the adopted edition with the authority having jurisdiction and a qualified code professional.
Privacy: calculations run locally in your browser; values are not submitted by this tool.
Capacity Factors and Minimum Widths
| Code / occupancy | Stairways | Doors, corridors, ramps |
|---|---|---|
| IBC 1005.3, standard | 0.3 in/person | 0.2 in/person |
| IBC, sprinklered + EVACS (not H, I-2) | 0.2 in/person | 0.15 in/person |
| NFPA 101, most occupancies | 0.3 in/person | 0.2 in/person |
| NFPA 101, board and care | 0.4 in/person | 0.2 in/person |
| NFPA 101, health care nonsprinklered | 0.6 in/person | 0.5 in/person |
| NFPA 101, high-hazard contents | 0.7 in/person | 0.4 in/person |
IBC minimum widths: stairway 44 in, or 36 in serving fewer than 50 occupants (1011.2); door 32 in clear (1010.1.1); corridor 44 in general, 36 in under 50 occupants or in a dwelling unit, 72 in Group E with 100 or more, 96 in I-2 bed movement (Table 1020.3); ramp 36 in between handrails (1012.5.1). NFPA 101 uses 44 in (36 in under 50) for new stairs, 32 in for doors and 44 in for new ramps; corridor widths come from the occupancy chapter.
Sources: 2024 IBC Chapter 10 (ICC); NFPA 101 Life Safety Code, Table 7.3.3.1.
How Many People Can a Door or Stair Serve?
Occupant capacity = clear width ÷ factor, rounded down. Minimum widths still apply.
| Clear width | Stair 0.3 | Stair 0.2 | Door/corridor 0.2 | Door/corridor 0.15 |
|---|---|---|---|---|
| 32 in (813 mm) | 106 | 160 | 160 | 213 |
| 34 in (864 mm) | 113 | 170 | 170 | 226 |
| 36 in (914 mm) | 120 | 180 | 180 | 240 |
| 44 in (1,118 mm) | 146 | 220 | 220 | 293 |
| 48 in (1,219 mm) | 160 | 240 | 240 | 320 |
| 56 in (1,422 mm) | 186 | 280 | 280 | 373 |
| 64 in (1,626 mm) | 213 | 320 | 320 | 426 |
| 72 in (1,829 mm) | 240 | 360 | 360 | 480 |
| 88 in (2,235 mm) | 293 | 440 | 440 | 586 |
| 96 in (2,438 mm) | 320 | 480 | 480 | 640 |
Quick answer
Required egress width is the larger of two checks: capacity width (occupant load × 0.3 in per person for stairways, 0.2 in for doors, corridors and ramps, IBC 1005.3) and the dimensional minimum for the component (44 in stair, 32 in clear door, 44 in corridor in most occupancies). With a qualifying sprinkler and voice alarm system the IBC factors drop to 0.2 and 0.15.
Examples
| Occupant load | Door or corridor (0.2 in) | Stairway (0.3 in) |
|---|---|---|
| 100 | 20 in → 32 in door min | 30 in → 44 in stair min |
| 250 | 50 in | 75 in |
| 450 | 90 in | 135 in |
| 500 | 100 in | 150 in |
Enter your occupant load and component to get the governing width, the width per exit and the capacity of existing openings.
Summary
Get the required egress width from the occupant load (the larger of capacity width and the code minimum), split it across exits, or check how many people existing doors and stairs can serve.
How it works
- Enter the occupant load served by the component being checked. For a stairway, use the largest single story it serves, not the sum of all stories (IBC 1005.3.1).
- Choose IBC 2024 or NFPA 101, the component and, for NFPA, the occupancy that sets the capacity factor.
- Capacity width = occupant load × factor. The required width is the larger of that and the dimensional minimum for the component.
- Enter the number of exits to see the width each needs if the load is shared equally.
- Optionally list existing clear widths (for example "36, 44") to get their combined capacity, check each against the minimum and test the 50% loss-of-one-exit rule (IBC 1005.5).
Use cases
- Size stairways, doors and corridors from an occupant load during early design.
- Check how many occupants an existing door or stair can serve.
- Compare the IBC sprinklered reduction with the standard factor.
- Check whether losing the largest exit still leaves half the required capacity.
- Compare IBC and NFPA 101 capacity factors for health care and high-hazard occupancies.