Flame Spread Index Classifier

Enter the FSI and SDI from a product test report to identify whether the values fall within the displayed Class A, B or C thresholds.

Use the Flame Spread Index Classifier

FSI & SDI report interpreter

Enter whole-number indices from the exact ASTM E84 or UL 723 report. Both fields are required.

Use the reported index, not a material estimate.

A/B/C each require SDI 0–450.

Interior finish classification thresholds

ClassFSISDI
A0–250–450
B26–750–450
C76–2000–450

These are the displayed ICC thresholds for interior wall and ceiling finish classification. They do not state which class your project requires.

What the indices represent

ASTM E84 is a comparative, controlled surface-burning test. Select-grade red oak and fiber-cement board surfaces provide reference behavior. The method reports FSI and SDI, but ASTM notes that the two measurements are not necessarily related.

  • It does not measure heat transmission through the surface.
  • FSI alone does not establish that a material is noncombustible.
  • Mounting, support, thickness, facing and assembly details can affect the reported result.
  • It is not the same as an hourly fire-resistance rating.

Primary references

Summary

Enter the FSI and SDI from a product test report to identify whether the values fall within the displayed Class A, B or C thresholds.

How it works

  1. Find the reported FSI and SDI on the exact product or assembly test report.
  2. Enter both whole-number indices; neither value is optional for this classification check.
  3. The tool compares them with the displayed Class A, B and C interior-finish thresholds.
  4. Review the result explanation and the ASTM E84 scope limitations.
  5. Confirm the required class, test method, assembly and adopted code with the authority having jurisdiction.

Use cases

  • Understand what a reported flame spread index of 25 means when SDI is also known.
  • Check the boundary between Class A, B and C interior wall or ceiling finish classifications.
  • Identify when SDI above 450 prevents an A/B/C result even if FSI is low.
  • Explain why an ASTM E84 index is not a fire-resistance rating or proof of noncombustibility.
  • Prepare questions for a manufacturer, testing laboratory or code official.

Frequently Asked Questions