Per Unit System Calc

Z_base = kV² ÷ MVA and I_base = MVA × 1000 ÷ (√3 × kV) for three-phase (MVA × 1000 ÷ kV for single-phase). On a 100 MVA, 138 kV base, Z_base = 190.44 Ω and I_base = 418.37 A, so 50 Ω = 0.2625 pu. Change of base: Z_new = Z_old × (kV_old ÷ kV_new)² × (MVA_new ÷ MVA_old); 0.10 pu on 50 MVA, 132 kV becomes 0.1830 pu on 100 MVA, 138 kV.

Use the Per Unit System Calc

Quantity Type

Direction

System Base

Base Change (Impedance)

Rescale a per-unit impedance from equipment base to system base.

Enter values on the left and click Calculate to see results.

Base voltage across a transformer

The base MVA is the same in every zone; the base kV steps by the transformer's rated voltage ratio. Uses the system base MVA and the phase setting above.

Zone Base kV Base Z (Ω) Base I (A)

Per-unit formulas

Base quantity Three-phase Single-phase
PowerS_base = MVA 3φS_base = MVA 1φ
VoltageV_base = kV line-to-lineV_base = kV of the circuit
CurrentI = MVA·1000 / (√3·kV)I = MVA·1000 / kV
ImpedanceZ = kV² / MVAZ = kV² / MVA
Change of baseZ_new = Z_old · (kV_old / kV_new)² · (MVA_new / MVA_old)
Fault behind ZI_f = I_base / Z_pu; S_f = MVA_base / Z_pu (1.0 pu prefault)

Worked example

System base 100 MVA, 138 kV (three-phase): Z_base = 138² ÷ 100 = 190.44 Ω and I_base = 100,000 ÷ (√3 × 138) = 418.37 A. A 50 Ω line is 50 ÷ 190.44 = 0.2625 pu, and 600 A is 600 ÷ 418.37 = 1.434 pu.

Change of base. A 50 MVA transformer with X = 10% on its 132 kV rating, on the 100 MVA, 138 kV base: 0.10 × (132/138)² × (100/50) = 0.10 × 0.9149 × 2 = 0.1830 pu, or 0.1830 × 190.44 = 34.85 Ω. A bolted fault behind it from a 1.0 pu infinite source draws 418.37 ÷ 0.1830 = 2,286 A, which is 100 ÷ 0.1830 = 546.5 MVA.

Across the transformer. With a 138/13.8 kV transformer, the low-side base is 13.8 kV, Z_base = 13.8² ÷ 100 = 1.9044 Ω and I_base = 4183.7 A. The per-unit values stay the same on both sides.

Copied!

Summary

The Per Unit System Calculator converts power system quantities (impedance, voltage, current and power) between actual values and per-unit (pu) values on a chosen base. Three-phase systems use three-phase MVA and line-to-line kV; single-phase systems use single-phase MVA and the single-phase voltage. It also rescales a per-unit or percent impedance from a nameplate base to the system base, reports the bolted fault current and fault MVA behind that impedance, and carries the base voltage across a transformer so every voltage zone has consistent bases. Everything runs in your browser.

How it works

  1. Choose three-phase (MVA 3φ, kV line-to-line) or single-phase (MVA 1φ, kV of the single-phase circuit).
  2. Enter the base MVA and base kV. The tool shows Z_base = kV² ÷ MVA, I_base and the base voltage.
  3. Pick a quantity (impedance, voltage, current or power) and a direction, enter the value, and click Calculate.
  4. For a change of base, enter the impedance in pu or % on the equipment base (MVA and kV) and the new system base.
  5. The base-change result also gives the ohmic value, plus the bolted fault current and fault MVA behind that impedance at 1.0 pu voltage.
  6. In the transformer section, the base voltage on the far side = base kV × (rated kV far side ÷ rated kV near side).

Use cases

  • Convert transformer and generator nameplate impedances (%Z) to a common system base.
  • Compute base impedance and base current for a bus voltage level.
  • Convert per-unit load-flow or fault-study results back to amps, kV and MVA.
  • Estimate the fault current at a transformer secondary from its percent impedance.
  • Carry base voltages through transformers into each zone of a one-line diagram.
  • Check single-phase distribution transformer impedances in per unit.