Short Circuit Current Calculator
Calculate the available bolted short-circuit (fault) current at a transformer secondary given kVA rating, primary voltage, and percent impedance.
System Parameters
Typically 2–6%; found on transformer nameplate.
Short-circuit MVA of the utility at the primary bus.
Enter system parameters and click Calculate to see results.
Available Bolted Fault Current
—
kA (rms sym.)
Calculation Details
- Full-Load Current (FLA)
- —
- Transformer Base Impedance
- —
- Transformer Z (per-unit)
- —
- Total Z (per-unit)
- —
- Short-Circuit MVA
- —
- Asymmetrical Peak (×1.6)
- —
Formula Reference
Copied!
Summary
Calculate the available bolted short-circuit (fault) current at a transformer secondary given kVA rating, primary voltage, and percent impedance.
How it works
- Enter the transformer kVA rating (e.g. 500 kVA for a 500 kVA transformer).
- Enter the secondary line-to-line voltage in volts (e.g. 480 V for a typical low-voltage system).
- Select the system type: single-phase or three-phase.
- Enter the transformer percent impedance (%Z), typically 2–6% from the nameplate.
- Optionally enter the source impedance at the primary side to account for utility contribution.
- Click Calculate to see the available bolted fault current in kA and A.
Use cases
- Size circuit breakers and fuses for an electrical panel.
- Verify that switchgear interrupting ratings exceed the available fault current.
- Perform NEC and IEC arc-flash hazard assessments.
- Validate transformer protection coordination studies.
- Check bus ratings in motor control centers (MCCs).
- Estimate fault current for new distribution transformer installations.
- Design low-voltage power distribution for commercial buildings.
- Compare fault levels before and after adding a second parallel transformer.
Frequently Asked Questions
Last updated: 2026-06-11 ·
Reviewed by Nham Vu