Transformer Sizing Calculator

Single-phase kVA = V × I ÷ 1000; three-phase kVA = √3 × V × I ÷ 1000 (or kVA = kW ÷ PF). Multiply by 1.25 for continuous loads and add a growth allowance, then pick the next standard size. Example: 100 A at 480 V three-phase = 83.1 kVA; with 25% growth → 103.9 kVA → 112.5 kVA, 135.3 A secondary.

Use the Transformer Sizing Calculator

Load & System Parameters

Circuit Configuration

Spare capacity for future load (0–100%). Applied after the continuous-load factor.

Sizing Summary

Enter load parameters and click Calculate.

Transformer full-load amps: three-phase

FLA = kVA × 1000 ÷ (1.732 × VLL).

kVA 208 V240 V480 V600 V
15 41.636.118.014.4
30 83.372.236.128.9
45 124.9108.354.143.3
75 208.2180.490.272.2
112.5 312.3270.6135.3108.3
150 416.4360.8180.4144.3
225 624.5541.3270.6216.5
300 832.7721.7360.8288.7
500 1,387.91,202.8601.4481.1
750 2,081.81,804.2902.1721.7
1000 2,775.72,405.61,202.8962.3
1500 4,163.63,608.41,804.21,443.4

Transformer full-load amps: single-phase

FLA = kVA × 1000 ÷ V.

kVA 120 V240 V277 V480 V
5 41.720.818.110.4
10 83.341.736.120.8
15 125.062.554.231.3
25 208.3104.290.352.1
37.5 312.5156.3135.478.1
50 416.7208.3180.5104.2
75 625.0312.5270.8156.3
100 833.3416.7361.0208.3
167 1,391.7695.8602.9347.9
250 2,083.31,041.7902.5520.8

Worked examples

Three-phase from amps. 100 A at 480 V: 1.732 × 480 × 100 ÷ 1000 = 83.1 kVA. With 25% growth: 103.9 kVA → 112.5 kVA standard. Secondary FLA = 112,500 ÷ (1.732 × 480) = 135.3 A, so the load is 73.9% of rating.

Continuous kW load, step-down. 60 kW at 0.85 PF, continuous, 0% growth, 480 V to 208Y/120 V: 60 ÷ 0.85 = 70.6 kVA × 1.25 = 88.2 kVA → 112.5 kVA. FLA is 312.3 A at 208 V and 135.3 A at 480 V. Primary-only protection: 125% × 135.3 = 169.1 A → 175 A maximum.

Single-phase. 80 A at 240 V = 19.2 kVA; with 25% growth 24.0 kVA → 25 kVA, FLA 104.2 A.

Standard ratings follow ANSI/IEEE C57.12.00 preferred kVA ratings and common dry-type catalogs; three-phase ratings above 1500 kVA are usually liquid-filled pad-mount or substation units. Not a substitute for an engineered load calculation.

Summary

This calculator converts a load given in amps, in kW with a power factor, or directly in kVA into the apparent power a transformer must supply, applies an optional 125% continuous-load factor and a growth allowance, and selects the next standard ANSI/NEMA kVA rating. It then reports secondary and primary full-load current, percent loading, spare capacity, and the maximum overcurrent device ratings allowed by NEC Table 450.3(B) for transformers rated 1000 V or less.

How it works

  1. Choose single-phase or balanced three-phase, and how you know the load: amps, kW with power factor, or kVA.
  2. Enter the secondary (load-side) voltage and, optionally, the primary voltage for primary full-load current.
  3. Tick "continuous load" to size at 125%, and set a growth allowance (default 25%).
  4. Load kVA = V × I ÷ 1000 (single-phase) or √3 × V × I ÷ 1000 (three-phase); from kW, kVA = kW ÷ PF.
  5. Required kVA = load kVA × 1.25 (if continuous) × (1 + growth %). The next standard rating at or above it is selected, and FLA = kVA × 1000 ÷ V (÷ √3 for three-phase).

Use cases

  • Preliminary sizing of a dry-type distribution transformer for a panel or building addition.
  • Finding the kVA needed for a kW load at a given power factor.
  • Getting primary and secondary full-load amps for a 480–208Y/120 V step-down transformer.
  • Checking how loaded an existing transformer is and how much spare capacity remains.
  • Estimating maximum primary and secondary overcurrent device sizes under NEC 450.3(B).

Frequently Asked Questions

Last updated: 2026-10-10 · Reviewed by Nham Vu