Transformer Sizing Calculator
Single-phase kVA = V × I ÷ 1000; three-phase kVA = √3 × V × I ÷ 1000 (or kVA = kW ÷ PF). Multiply by 1.25 for continuous loads and add a growth allowance, then pick the next standard size. Example: 100 A at 480 V three-phase = 83.1 kVA; with 25% growth → 103.9 kVA → 112.5 kVA, 135.3 A secondary.
Use the Transformer Sizing Calculator
Load & System Parameters
Spare capacity for future load (0–100%). Applied after the continuous-load factor.
Sizing Summary
Enter load parameters and click Calculate.
Recommended Standard Rating
Maximum overcurrent protection, NEC 450.3(B)
For transformers rated 1000 V or less. Standard sizes per NEC 240.6(A). Conductor ampacity, inrush, and the code edition adopted locally still govern.
Transformer full-load amps: three-phase
FLA = kVA × 1000 ÷ (1.732 × VLL).
| kVA | 208 V | 240 V | 480 V | 600 V |
|---|---|---|---|---|
| 15 | 41.6 | 36.1 | 18.0 | 14.4 |
| 30 | 83.3 | 72.2 | 36.1 | 28.9 |
| 45 | 124.9 | 108.3 | 54.1 | 43.3 |
| 75 | 208.2 | 180.4 | 90.2 | 72.2 |
| 112.5 | 312.3 | 270.6 | 135.3 | 108.3 |
| 150 | 416.4 | 360.8 | 180.4 | 144.3 |
| 225 | 624.5 | 541.3 | 270.6 | 216.5 |
| 300 | 832.7 | 721.7 | 360.8 | 288.7 |
| 500 | 1,387.9 | 1,202.8 | 601.4 | 481.1 |
| 750 | 2,081.8 | 1,804.2 | 902.1 | 721.7 |
| 1000 | 2,775.7 | 2,405.6 | 1,202.8 | 962.3 |
| 1500 | 4,163.6 | 3,608.4 | 1,804.2 | 1,443.4 |
Transformer full-load amps: single-phase
FLA = kVA × 1000 ÷ V.
| kVA | 120 V | 240 V | 277 V | 480 V |
|---|---|---|---|---|
| 5 | 41.7 | 20.8 | 18.1 | 10.4 |
| 10 | 83.3 | 41.7 | 36.1 | 20.8 |
| 15 | 125.0 | 62.5 | 54.2 | 31.3 |
| 25 | 208.3 | 104.2 | 90.3 | 52.1 |
| 37.5 | 312.5 | 156.3 | 135.4 | 78.1 |
| 50 | 416.7 | 208.3 | 180.5 | 104.2 |
| 75 | 625.0 | 312.5 | 270.8 | 156.3 |
| 100 | 833.3 | 416.7 | 361.0 | 208.3 |
| 167 | 1,391.7 | 695.8 | 602.9 | 347.9 |
| 250 | 2,083.3 | 1,041.7 | 902.5 | 520.8 |
Worked examples
Three-phase from amps. 100 A at 480 V: 1.732 × 480 × 100 ÷ 1000 = 83.1 kVA. With 25% growth: 103.9 kVA → 112.5 kVA standard. Secondary FLA = 112,500 ÷ (1.732 × 480) = 135.3 A, so the load is 73.9% of rating.
Continuous kW load, step-down. 60 kW at 0.85 PF, continuous, 0% growth, 480 V to 208Y/120 V: 60 ÷ 0.85 = 70.6 kVA × 1.25 = 88.2 kVA → 112.5 kVA. FLA is 312.3 A at 208 V and 135.3 A at 480 V. Primary-only protection: 125% × 135.3 = 169.1 A → 175 A maximum.
Single-phase. 80 A at 240 V = 19.2 kVA; with 25% growth 24.0 kVA → 25 kVA, FLA 104.2 A.
Standard ratings follow ANSI/IEEE C57.12.00 preferred kVA ratings and common dry-type catalogs; three-phase ratings above 1500 kVA are usually liquid-filled pad-mount or substation units. Not a substitute for an engineered load calculation.
Summary
This calculator converts a load given in amps, in kW with a power factor, or directly in kVA into the apparent power a transformer must supply, applies an optional 125% continuous-load factor and a growth allowance, and selects the next standard ANSI/NEMA kVA rating. It then reports secondary and primary full-load current, percent loading, spare capacity, and the maximum overcurrent device ratings allowed by NEC Table 450.3(B) for transformers rated 1000 V or less.
How it works
- Choose single-phase or balanced three-phase, and how you know the load: amps, kW with power factor, or kVA.
- Enter the secondary (load-side) voltage and, optionally, the primary voltage for primary full-load current.
- Tick "continuous load" to size at 125%, and set a growth allowance (default 25%).
- Load kVA = V × I ÷ 1000 (single-phase) or √3 × V × I ÷ 1000 (three-phase); from kW, kVA = kW ÷ PF.
- Required kVA = load kVA × 1.25 (if continuous) × (1 + growth %). The next standard rating at or above it is selected, and FLA = kVA × 1000 ÷ V (÷ √3 for three-phase).
Use cases
- Preliminary sizing of a dry-type distribution transformer for a panel or building addition.
- Finding the kVA needed for a kW load at a given power factor.
- Getting primary and secondary full-load amps for a 480–208Y/120 V step-down transformer.
- Checking how loaded an existing transformer is and how much spare capacity remains.
- Estimating maximum primary and secondary overcurrent device sizes under NEC 450.3(B).