Motor Full-Load Amps Calculator

Enter motor horsepower (or kW), voltage and phase to get the NEC table full-load current, then the 250% breaker, 175% fuse, 125% conductor size in AWG and the nameplate-based overload setting.

Motor full-load amps for circuit sizing come from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase), not the nameplate: a 10 HP, 460 V three-phase motor is 14 A and a 1 HP, 230 V single-phase motor is 8 A.

Use the Motor Full-Load Amps Calculator

Motor Parameters

Motor Phase

Overload sizing (optional, NEC 430.32)

Formula estimate (comparison only)

Results

Enter motor parameters and click Calculate.

NEC Motor Full-Load Current Tables

Full-load current in amperes. The calculator highlights the row it used.

Table 430.248 — Single-Phase AC Motors

HP 115 V 200 V 208 V 230 V
1/6 4.4 2.5 2.4 2.2
1/4 5.8 3.3 3.2 2.9
1/3 7.2 4.1 4 3.6
1/2 9.8 5.6 5.4 4.9
3/4 13.8 7.9 7.6 6.9
1 16 9.2 8.8 8
1-1/2 20 11.5 11 10
2 24 13.8 13.2 12
3 34 19.6 18.7 17
5 56 32.2 30.8 28
7-1/2 80 46 44 40
10 100 57.5 55 50

Table 430.250 — Three-Phase AC Induction Motors

HP 115 V 200 V 208 V 230 V 460 V 575 V 2300 V
1/2 4.4 2.5 2.4 2.2 1.1 0.9 —
3/4 6.4 3.7 3.5 3.2 1.6 1.3 —
1 8.4 4.8 4.6 4.2 2.1 1.7 —
1-1/2 12 6.9 6.6 6 3 2.4 —
2 13.6 7.8 7.5 6.8 3.4 2.7 —
3 — 11 10.6 9.6 4.8 3.9 —
5 — 17.5 16.7 15.2 7.6 6.1 —
7-1/2 — 25.3 24.2 22 11 9 —
10 — 32.2 30.8 28 14 11 —
15 — 48.3 46.2 42 21 17 —
20 — 62.1 59.4 54 27 22 —
25 — 78.2 74.8 68 34 27 —
30 — 92 88 80 40 32 —
40 — 120 114 104 52 41 —
50 — 150 143 130 65 52 —
60 — 177 169 154 77 62 16
75 — 221 211 192 96 77 20
100 — 285 273 248 124 99 26
125 — 359 343 312 156 125 31
150 — 414 396 360 180 144 37
200 — 552 528 480 240 192 49
250 — — — — 302 242 60
300 — — — — 361 289 72
350 — — — — 414 336 83
400 — — — — 477 382 95
450 — — — — 515 412 103
500 — — — — 590 472 118

Use the 110–120, 220–240 and 440–480 V system voltages with the 115, 230 and 460 V columns (Table 430.248/430.250 notes). Synchronous motors, DC motors (Table 430.247) and low-speed, high-torque or multispeed motors are not covered.

Quick answer

Motor full-load amps for circuit sizing come from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase), not the nameplate: a 10 HP, 460 V three-phase motor is 14 A and a 1 HP, 230 V single-phase motor is 8 A. Conductors are sized at 125% of that current (430.22) and an inverse-time breaker at up to 250% (430.52), rounded up to the next standard size.

Examples

MotorNEC FLA125% conductor (75 °C Cu)250% breaker
1 HP, 230 V, 1-phase8 A10 A → 14 AWG20 A
5 HP, 230 V, 1-phase28 A35 A → 10 AWG70 A
5 HP, 208 V, 3-phase16.7 A20.9 A → 12 AWG45 A
10 HP, 230 V, 3-phase28 A35 A → 10 AWG70 A
10 HP, 460 V, 3-phase14 A17.5 A → 14 AWG35 A
50 HP, 460 V, 3-phase65 A81.3 A → 4 AWG175 A

Pick phase and voltage, enter HP or kW, and add the nameplate amps to get the overload setting too.

Summary

Enter motor horsepower (or kW), voltage and phase to get the NEC table full-load current, then the 250% breaker, 175% fuse, 125% conductor size in AWG and the nameplate-based overload setting.

How it works

  1. Select single-phase or three-phase and the motor voltage (115–2300 V).
  2. Enter the rating in horsepower, or in kW (converted at 1 HP = 746 W).
  3. The calculator reads the full-load current from NEC Table 430.248 or 430.250. A rating between two table rows uses the next larger listed horsepower, which is the conservative choice.
  4. Branch-circuit protection: 250% for an inverse-time breaker and 175% for a dual-element time-delay fuse (Table 430.52(C)(1)), rounded up to the next standard size in 240.6(A).
  5. Conductor: 125% of the table current (430.22), matched to the smallest copper size in Table 310.16 for 60 °C and 75 °C terminations (600 V and below).
  6. Overload: enter the nameplate current and choose the service factor or temperature-rise marking to get the 115% or 125% setting from 430.32(A)(1).
  7. Optional estimate: I = HP × 746 ÷ (V × efficiency × power factor), times √3 in the denominator for three-phase. It is shown for comparison only.

Use cases

  • Size branch-circuit breakers and fuses per NEC 430.52.
  • Find the wire size for a motor using the 125% conductor rule (NEC 430.22).
  • Set a motor overload relay from nameplate current and service factor (NEC 430.32).
  • Check a motor nameplate FLA against the NEC table value.
  • Convert an IEC kW motor rating to the NEC horsepower row.
  • Calculate service-entrance load for multiple motors.
  • Pre-fill permit applications that require NEC FLA values.