Conduit Fill Calculator

Select conduit type and trade size, add conductors by AWG, and instantly see the fill percentage against NEC 2023 limits.

NEC Chapter 9 Table 1 limits conduit fill to 40% of the inside area for 3 or more conductors, 31% for 2 and 53% for 1.

Use the Conduit Fill Calculator

Conduit Configuration

Conductors

Fill Result

Configure conduit and add conductors, then click Calculate Fill.

NEC 2023 Chapter 9, Table 1 — Fill Limits
53%
1 conductor
31%
2 conductors
40%
3+ conductors

Quick answer

NEC Chapter 9 Table 1 limits conduit fill to 40% of the inside area for 3 or more conductors, 31% for 2 and 53% for 1. Add up the wire areas (Table 5), divide by the conduit area (Table 4) and compare.

Examples

ConduitWires (THHN)FillResult
1/2 in EMT9 × #1239.4%Pass
1/2 in EMT10 × #1243.8%Fail
3/4 in EMT16 × #1239.9%Pass
3/4 in EMT10 × #1039.6%Pass
1 in EMT16 × #1039.1%Pass

Add your wires and conduit.

Summary

This conduit fill calculator applies NEC 2023 Chapter 9 Table 1 limits to EMT, IMC, and RMC conduit types. Enter the trade size and add conductors by AWG size and quantity; the tool computes total conductor area, allowable fill area, and the resulting percentage as a planning estimate. Verify the adopted code edition and installation with the authority having jurisdiction or a qualified electrician.

How it works

  1. Select the conduit type: EMT, IMC, or RMC.
  2. Pick the trade size (½" through 4") from the dropdown.
  3. Add each conductor group: choose AWG size and enter the quantity.
  4. The calculator sums the total conductor area and divides by the conduit internal area.
  5. Compare the result against NEC 2023 Chapter 9 Table 1 limits (40% for 3+ conductors, 31% for 2, 53% for 1). When all conductors are the same size, Note 7 rounds a calculated count with a decimal of 0.8 or more up to the next whole number.
  6. Adjust conductor count or trade size until the fill is within the allowed limit.

Use cases

  • Verify a panel feeder conduit is not over-filled before pulling wire.
  • Size a new conduit run for a given set of branch circuit conductors.
  • Check compliance when adding circuits to an existing conduit.
  • Quickly compare EMT vs. RMC fill for the same conductor bundle.
  • Confirm a homerun conduit meets NEC 40% fill rule before rough-in.

Frequently Asked Questions

Last updated: 2026-06-11 · Reviewed by Nham Vu